Name
Range
Step
Default
Open field
circuit
monitoring
0: Disabled
1: Enabled
-
0:
Disabled
Enables and disables the monitoring of open circuits in
the excitation winding.
The supervision is triggered when the control signal
exceeds the "Open field detection control signal high
threshold" parameter, while the field current is below the
"Open field detection field current low threshold"
parameter.
If open circuits are monitored and the above-
mentioned parameter conditions are met (high threshold
> I < low threshold), the Generator commander
performs a rectifier trip and stops the excitation after the
set time in the "Open field detection time delay"
parameter.
Open field
detection time
delay
0.000…10.000s
0.005s
3.000s
Determines the time delay for the open field detection.
Open field
detection
control signal
high threshold
0.00…25.00
0.01
1.00
Determines the high threshold for the open field
detection control signal.
If the current exceeds this threshold, one of the
parameter conditions for open field detection is met.
Open field
detection field
current low
threshold
0.00…25.00
0.01
0.10
Determines the low threshold for the open field
detection's control signal.
If the current does not exceed this threshold, one of the
parameter conditions for open field detection is met.
Miscellaneous
Alarm level for
IGBT
temperature
0…200
1
100
Determines the alarm level for the IGBT temperature.
This supervision protects the insulated gate bipolar
transistor (IGBT) of the AQ-GC30 rectifier unit from
overheating.
This supervision is always active.
Internal
tripping of
field breaker
0: Disabled
1: Enabled
-
0:
Disabled
Enables and disables the internal tripping of the field
breaker.
When enabled, if the machine circuit control is open, an
OFF signal from the selected field breaker runs down
the excitation current and opens the field breaker
once the set "Inverter mode time on stopping" has
passed.
The trip control is also supervised: if the field breaker is
not open within the set "Open field breaker trip
time" delay, the unit issues an event.
Open field
breaker trip
time
0.0…1800.0s
0.1s
0.5s
Determines the delay time between a TRIP signal and
the field breaker's "Open" status.
Inverter mode
time on
stopping
0.0…10.0s
0.1s
1.0s
Determines the operation time to shut the converter
down.
Open loop
adjustment
speed
0.00…1.00p.u./s
0.00p.u./s 0.02p.u./s
Determines the speed at which the control signal rises
and falls when the "OpnLoopRef" option for the "Force
OWM controlsignal" parameter is selected (can be
found at
Excitation
→
Excitation internal parameters
→
"Excitation constants").
Note that this parameter is for testing purposes only!
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
430
© Arcteq Relays Ltd
IM00001