Name
Range
Step
Default
Description
Adjustment
slew of
reference
when
synchronized
(generator
voltage/
second)
0.000…1.000p.u./s
0.001p.u./s
0.002p.u./s
Defines the speed at which the adjustment
pulses increase or decrease the AVR reference
value, when the AVR is synchronized to a grid.
Adjustment
slew of
reference
when not
synchronized
(generator
voltage/
second)
0.000…1.000p.u./s
0.001p.u./s
0.005p.u./s
Defines the speed at which the adjustment
pulses increase or decrease the AVR reference
value, when the AVR is not synchronized to a
grid.
Enable voltage
matching
0: Disabled
1: Enabled
-
0: Disabled
Enables and disables the voltage matching.
When voltage matching is enabled and an input
signal for voltage matching is selected, the
Generator commander matches the generator
voltage with the selected voltage matching
reference, as defined by the "Voltage matching
reference select" parameter.
Voltage
matching
reference
select
0: U3
1: U4
-
U3
Defines the reference channel from which the
voltage is read for voltage matching.
This setting is only visible when "Enable voltage
matching" has been enabled.
Voltage
matching
status
0: Excitation is ON
1: Not synchronized
2: Synchronized
3: Grid voltage too low
4: Low measured voltage
5: Field breaker is open
6: Test mode is ON
7: Voltage matching
enabled
8: Voltage matching
commanded
9: Generator voltage OK
for matching
10: Following line voltage
ON
-
-
Displays the status of the voltage matching.
This setting is only visible when "Enable voltage
matching" has been enabled.
Measured grid
voltage now
-500.00…500.00p.u.
0.01p.u.
-
Displays the measured grid voltage at the
moment.
This setting is only visible when "Enable voltage
matching" has been enabled.
Measured
generator
voltage now
-500.00…500.00p.u.
0.01p.u.
-
Displays the measured generator voltage at the
moment.
This setting is only visible when "Enable voltage
matching" has been enabled.
Field current regulator
The FCR (field current regulator) is also known as manual control. It is used as a backup for the AVR
control mode as well as for testing purposes. In the FCR mode the excitation current is kept constant
according to the reference value regardless of what the network voltage or active power is. The
generator voltage changes according to the active power and to the grid voltage.
The diagram below depicts the transfer function of the field current regulator.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
433