Table. 6.2.2.4 - 373. The AI status of the local/remote bridge ("Bridge A/B AI status").
Name
Range
Step
Default
Description
Bridge A/B mA
input value
0.000…20.000mA 0.001mA 0mA
Displays the milliampere input value of the local/remote
bridge, when (for example) controlling the AQ-GC30 rectifier
unit through logic.
Bridge A/B U input
value
0.000…10.000V
0.001V
0V
Displays the voltage input value of the local/bridge bridge,
when (for example) controlling the AQ-GC30 rectifier unit
through logic.
Bridge A/B IGBT
temperature
0.00…500.00ºC
0.01ºC
0ºC
Displays the temperature measurement value of the local/
remote bridge.
Bridge A/B DC link
voltage (raw)
0.00…500.00VDC 0.01VDC 0VDC
Displays the DC link voltage measurement value of the local/
remote bridge.
Please note that this parameter is named "DC link voltage" in
the settings for the remote (B) bridge.
Bridge A DC link
voltage filter
0: Enabled
1: Disabled
-
0:
Enabled
Enables or disables the DC link voltage measuring filter of
the local (A) bridge.
See also the parameter "Bridge A/B DC link voltage filter time
constant".
Please note that this setting is only available for the local (A)
bridge.
Bridge A DC link
voltage filter time
constant
0.000…1800.000s 0.005s
0.02s
Defines the time constant for the DC link voltage measuring
filter of local (A) bridge.
See also the parameter "Bridge A/B DC link voltage filter".
Please note that this setting is only available for the local (A)
bridge.
Bridge A DC link
voltage (filtered)
0.000…500.000V
0.001V
0V
Displays the DC link voltage filtered measurement value of
the local (A) bridge. This current is the supply voltage as V
(DC).
Please note that this setting is only available for the local (A)
bridge.
Bridge A/B DC link
current (raw)
0.000…500.000A
0.001A
0A
Displays the DC link current measurement value of the local/
remote bridge. This current is the excitation current.
Bridge A/B DC link
current filter
0: Enabled
1: Disabled
-
0:
Enabled
Enables and disables the DC link current measuring filter of
the local/remote bridge.
See also the parameter "Bridge A/B DC link current filter time
constant".
Bridge A/B DC link
filter time constant 0.000…1800.000s 0.005s
0.02s
Defines the time constant for the DC link current measuring
filter of the local/remote bridge.
See also the parameter "Bridge A/B DC link current filter".
Bridge A/B DC link
current (filtered)
0.000…500.000A
0.001A
0A
Displays the DC link current filtered measurement value of
the local/remote bridge. This current is the excitation
current.
Bridge A/B supply
voltage
0.0…500.0V
0.1V
0V
Defines the supply voltage of the local/remote bridge.