Events and registers
The total harmonic distortion monitor function (abbreviated "THD" in event block names) generates
events and registers from the status changes in the alarm function when it is activated. The recorded
signals are START and ALARM signals for the monitoring elements as well as common BLOCKED
signals. The user can select which event messages are stored in the main event buffer: ON, OFF, or
both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.6.4 - 314. Event messages.
Event block name
Event names
THD1
THD Start Phase ON
THD1
THD Start Phase OFF
THD1
THD Start I01 ON
THD1
THD Start I01 OFF
THD1
THD Start I02 ON
THD1
THD Start I02 OFF
THD1
THD Alarm Phase ON
THD1
THD Alarm Phase OFF
THD1
THD Alarm I01 ON
THD1
THD Alarm I01 OFF
THD1
THD Alarm I02 ON
THD1
THD Alarm I02 OFF
THD1
Blocked ON
THD1
Blocked OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, ALARM and BLOCKED. The table below
presents the structure of the function's register content.
Table. 5.6.4 - 315. Register content.
Date and time
Event
L1h, L2h, L3h Fault THD
Used SG
dd.mm.yyyy hh:mm:ss.mss
Event name
Start/Alarm THD of each phase.
Setting group 1...8 active.
5.6.5 Voltage total harmonic distortion (THD)
The voltage total harmonic distortion (THD) function is used for monitoring the content of the voltage
harmonic. The THD is a measurement of the harmonic distortion present, and it is defined as the ratio
between the sum of all harmonic components' powers and the power of the fundamental frequency
(RMS).
Harmonics can be caused by different sources in electric networks such as electric machine drives,
thyristor controls, etc. The function's monitoring of the voltage can be used to alarm of the harmonic
content rising too high; this can occur when there is an electric quality requirement in the protected
unit, or when the harmonics generated by the process need to be monitored.