Measurement scaling coefficients
The measurement scaling coefficients are available for the following measurements, in addition to the
general measurement scaling coefficient:
• Active energy
• Reactive energy
• Active power
• Reactive power
• Apparent power
• Power factor
• Frequency
• Current
• Residual current
• Voltage
• Residual voltage
• Angle
The range is the same for all of the scaling coefficients. By default, there is no scaling.
• No scaling
• 1/10
• 1/100
• 1/1000
• 1/10 000
• 1/100 000
• 1/1 000 000
• 10
• 100
• 1000
• 10 000
• 100 000
• 1 000 000
Deadband settings.
Table. 7.1.9 - 404. Analog change deadband settings.
Name
Range
Step
Default
Description
General deadband
0.1…10.0%
0.1%
2%
Determines the general data reporting deadband settings.
Active energy deadband
0.1…1000.0kWh 0.1kWh 2kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0kW
0.1kW
2kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0kVA
0.1kVA
2kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00Hz
0.01Hz
0.1Hz
Determines the data reporting deadband settings for this
measurement.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
482
© Arcteq Relays Ltd
IM00001