General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.4.18 - 171. General settings of the function.
Name
Range
Step Default
Description
Q< LN mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
0: On
Set mode of UEX block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.
Q< measurement
selection
1: POW1
2: POW2
-
1:
POW1
Defines which power measurement module is used by the function.
This setting is available if the device has more than one current
measurement module.
Pick-up
The
Q
set
< setting parameter controls the pick-up of the Q< function. This defines the minimum allowed
measured three-phase reactive power before action from the function. The function constantly
calculates the ratio between the
Q
set
< and the measured magnitude (Q
m
). The reset ratio of 97 % is
built into the function and is always relative to the
Q
set
< value.
Table. 5.4.18 - 172. Pick-up settings.
Name
Range
Step
Default
Description
Qset mode
0: Fixed
1: P-
dependent
-
0: Fixed
Decides whether the pick-up area is defines only by the
Q
set
< parameter
or by two points set in the PQ plane.
Qset<
0.0…-100
000kvar
0.01kvar -100kvar
In Fixed mode: sets the pick-up value for the function.
In P-dependent mode: chooses the reactive power for the first point.
Pick-up P1
for Qset<
0.0…-100
000kW
0.01kW
100kW
The value of the active power for
Q
set
< when the P-dependent mode is
in use.
Qset2<
0.0…-100
000kvar
0.01kvar -100kvar Chooses the reactive power for the second point when the P-dependent
mode is in use.
Pick-up P2
for Qset<
0.0…-100
000kW
0.01kW
100kW
The value of the active power for
Q
set2
< when the P-dependent mode is
in use.
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
211
Содержание Generator Commander
Страница 1: ...Generator Commander Instruction manual...
Страница 2: ......