6.2.2.3 PP inputs to excitation
Table. 6.2.2.3 - 370. PP inputs of the excitation unit.
Input name
Description
Testmode ON
This input is used to switch on the test mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Command AVR
This input is used to switch on the AVR control mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Command FCR
This input is used to switch on the FCR control mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Command MVar
This input is used to switch on the MVar control mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Command PF
This input is used to switch on the PF control mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Increase
Defines the input that increases the reference values of the selected regulator function.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Decrease
Defines the input that decreases the reference values of the selected regulator function.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Field breaker
OFF
This input is used to open the field breaker.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Field breaker ON
This input is used to close the field breaker.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
Unload Mvar
This input is used to set reactive power to zero.
See also the parameter "Reactive power unload timeout" under the "MVAR" tab.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to
"PP control".
6.2.2.4 Local and remote bridge I/O
NO
NOTE!
TE!
Please note that in all the tables below "A" refers to a local bridge and "B" to a remote
bridge. This also applies to the parameter names and menu/submenu/tab names in the
AQtivate configuration and setting tool.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
451