Table. 6.2.2.4 - 371. Local/remote bridge communication ("Bridge A/B communication").
Name
Range
Step Default
Description
A/B receiver
GOOSE quality
0…2
32
–1
1
0
Displays the quality of the communication with the AQ-GC30 rectifier
unit. "0" is an indication of a healthy connection.
A/B receiver
application ID
0×0…0×3FFF 0×1
0×A1
Displays the virtual GOOSE address for communication with the AQ-
GC30 rectifier unit.
Please note that the A/B receivers must have different addresses,
e.g. ChA 0xA1 and ChB 0xA3.
A/B receiver
configuration
revision
0…2
32
–1
1
177
Displays the revision number of the configuration.
Please note that the A/B receivers must have different configuration
revisions, eg. ChA 177 and ChB 179.
Table. 6.2.2.4 - 372. The DI status of the local/remote bridge ("Bridge A/B DI status").
Name
Range Step Default
Description
Bridge A/B HW
system OK
0:
System
OK
1:
Failing
-
0:
System
OK
Indicates that the hardware system of the local/remote bridge is OK.
Bridge A/B
communication OK
0:
System
OK
1:
Failing
-
0:
System
OK
Indicates that the Generator commander has established a
communication connection to the local/remote bridge.
Bridge A/B health
status
0:
System
OK
1:
Failing
-
0:
System
OK
Indicates that the health status of the local/remote bridge is OK.
Bridge A DI1
0: Off
1: On
-
0: Off
Indicates the digital input status of the local/remote bridge.
Bridge A DI2
Bridge A DI3
Bridge A DI4
Bridge A DI5
Bridge A DI6
Bridge A DI7
Bridge A DI8
Bridge B DI1
Bridge B DI2
Bridge B DI3
Bridge B DI4
Bridge B DI5
Bridge B DI6
Bridge B DI7
Bridge B DI8
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
452
© Arcteq Relays Ltd
IM00001