The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.5.8 - 276. General settings of the function.
Name
Range
Default
Description
Δα LN mode
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
0: On
Set mode of VJP block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
Available
stages
0: Trip
1: Trip and alarm
0: Trip
Defines if alarm is included with trip or not.
Monitored
voltages
0: System all P-P
Voltages
1: System any P-P
Voltage
2: System L12
Voltage
3: System L23
Voltage
4: System L31
Voltage
5: System all P-E
voltages
6: System any P-E
voltage
7: System L1
Voltage
8: System L2
Voltage
9: System L3
Voltage
10: U4 Voltage
1: System any P-
P Voltage
Defines the monitored voltage channel(s)
Table. 5.5.8 - 277. Pick-up settings.
Name
Range
Step
Default
Description
Pick-up setting Δα (lead
or lag) Trip
0.05…30.00°
0.01°
5°
Pick-up setting for trip signal
Pick-up setting Δα (lead
or lag) Alarm
0.05…30.00°
0.01°
5°
Pick-up setting for alarm signal
Undervoltage block limit
% < Un
0.01…100.00%U
n
0.01%U
n
95%U
n
Block setting. When measured voltage is below this
setting the function is blocked.
The pick-up activation of the function is not directly equal to the START or TRIP signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
349