Table. 6.2.1.3.3 - 359. Setting parameters for reactive power control.
Name
Range
Step
Default
Description
MVAR control
status
0: MVAR mode ON
1: Synchronized Q
control OK
2: MVAR autoload on
start
3: MVAR start ref ON
4: Increase MVAR ON
5: Decrease MVAR ON
6: Unloading Q
7: Increase blocked
8: Decrease blocked
9: SCL overexcitation ON
10: SCL underexcitation
ON
11: FCL is on limit
12: VHz limiter active
13: UEL limiter active
14: MVAR ref on high
limit
15: MVAR ref on low limit
16: Tracking MVAR
reference
17: Increase command to
AVR/DCR ON
18: Decrease command
to AVR/FCR ON
-
-
Displays the status of the reactive power (MVAR)
control mode.
MVAR
reference now
-500.00…500.00p.u./p.u. 0.01p.u./p.u. 0.00p.u./p.u. Defines the MVAR reference at the moment.
Minimum MVAR
reference
allowed
-500.00…500.00p.u./p.u. 0.01p.u./p.u. 0.00p.u./p.u. Defines the minimum MVAR reference allowed.
Maximum
MVAR
reference
allowed
-500.00…500.00p.u./p.u. 0.01p.u./p.u. 0.00p.u./p.u. Defines the minimum MVAR reference allowed.
Reactive power
automatic
loading at
synchronizing
0: Disabled
1: Enabled
-
0: Disabled
Enables or disables the reactive power regulator,
as soon as the Generator commander gets the
“synchronized” signal.
Automatic
loading level
after
synchronizing
-1.00...1.00p.u.
0.01p.u.
-0.05p.u.
Defines the reference value for the reactive
power regulator, after synchronizing.
See also the parameter "Reactive power
automatic loading at synchronising".
MVAR controller
switches back
to AVR once
MvarRef
reached
0: Disabled
1: Enabled
-
0: Disabled
Enables and disables the switching to the AVR. If
enabled, this parameter switches the reactive
power regulator off as soon as the set MVAR
reference value is reached.
MVAR controller
minimum limit
-1.00...1.00p.u.
0.01p.u.
-0.30p.u.
Defines the minimum reactive power limit for the
MVAR controller.
The per-unit value is derived from the apparent
power of the machine.
MVAR controller
maximum limit
-1.00...1.00p.u.
0.01p.u.
0.60p.u.
Defines the maximum reactive power limit for the
MVAR controller.
The per-unit value is derived from the apparent
power of the machine.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
437