Sampling mode
Fixed
Tracking
Frequency reference 1
Frequency reference 2
Frequency reference 3
CT1IL1, CT2IL1, VT1U1, VT2U1
CT1IL2, CT2IL2, VT1U2, VT2U2
CT1IL3, CT2IL3, VT1U3, VT2U3
Pick-up
df/dt >/< pick-up setting
0.15…1.00 Hz/s, setting step 0.01 Hz
f> limit
10.00…70.00 Hz, setting step 0.01 Hz
f< limit
7.00…65.00 Hz, setting step 0.01 Hz
Pick-up inaccuracy
- df/dt
±5.0 %I
SET
or ±20 mHz/s
- frequency
±15 mHz (U > 30 V secondary)
±20 mHz (I > 30 % of rated secondary)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio +/- 50 mHz)
±1.5 % or ±110 ms (max. step size: 100 mHz)
Start time and instant operation time (trip):
- f
M
/f
SET
ratio +/- 20 mHz (overreach)
<200 ms
- f
M
/f
SET
ratio +/- 200 mHz (overreach)
<90 ms
Reset
f< and f> frequency limit
±0.020 Hz
df/dt
±10.0 % of pick-up or 50 mHz/s
Instant reset time and start-up reset:
- f
M
/f
SET
ratio +/- 50 mHz
<325 ms (max. step size: 100 mHz)
No
Notte!
e!
• Frequency is measured two seconds after a signal is received.
10.2.1.14 Machine thermal overload protection (TM>; 49M)
Table. 10.2.1.14 - 455. Technical data for the machine thermal overload protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
TRMS phase currents (up to the 31
st
harmonic)
Pick-up (Heating)
NPS bias factor (unbalance effect)
Pick-up current setting
Thermal alarm and trip level setting range
Motor service factor
0.1…10.0, setting step 0.1
0.10…40.00 × I
N
, setting step 0.01 × I
N
0.0…150.0 %, setting step 0.1 %
0.01…5.00 × I
N
, setting step 0.01 × I
N
Cold condition:
- Long heat T const (cold)
- Short heat T const (cold)
0.0…500.0 min, setting step 0.1 min
0.0…500.0 min, setting step 0.1 min
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
541