Name
Range
Step
Default
Description
Ind GB
closed
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the generator breaker can
be closed remotely and indicated as such.
Island mode
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the Generator commander
can be set to Island mode remotely.
Command
voltage
matching
(remote)
0: Off
1: On
-
0: Off
Selects whether or not a voltage matching
command can be given remotely.
Grid voltage
(remote)
0.00...500.00
0.01
0
Sets the grid voltage remotely.
Reset
remote
received
indications
0: -
1: Reset
-
0: -
Resets the received indications memory.
After resetting, the parameter returns back to "-".
Table. 6.2.3 - 380. Info out from excitation.
Name
Range
Step Default
Description
Field current
(remote)
–500.00…500.00 0.01
-
Displays the actual field current value.
AVR ref actual
(remote)
–500.00…500.00 0.01
-
Displays the actual AVR reference value.
FCR ref actual
(remote)
–500.00…500.00 0.01
-
Displays the actual FCR reference value.
MVar ref actual
(remote)
–500.00…500.00 0.01
-
Displays the actual MVar reference value.
PF ref actual
(remote)
–500.00…500.00 0.01
-
Displays the actual PF reference value.
Mode AVR (remote)
0: Off
1: On
-
0: Off
Indicates whether or not the AVR control mode can be directed
remotely.
Mode FCR (remote)
0: Off
1: On
-
0: Off
Indicates whether or not the FCR control mode can be directed
remotely.
Mode MVar (remote) 0: Off
1: On
-
0: Off
Indicates whether or not the MVar control mode can be directed
remotely.
Mode PF (remote)
0: Off
1: On
-
0: Off
Indicates whether or not the PF control mode can be directed
remotely.
Local control
Table. 6.2.3 - 381. Local control
Name
Range
Step
Default
Description
Control mode
0: DI control
1: PP control
2: Comm bus
control
-
0: DI
control
Indicates the selected control mode. The Generator
commander can be controlled locally through digital
inputs ("DI control"), through the process panel ("PP
control"), or through the remote bus ("Comm bus
control").
Scale panel
0.00…25
000.00p.u.
0.01p.u.
1.00p.u.
Scales the process panel values.
Step test enable/
Start test
0: Off
1: On
-
0: Off
Enables and disables the step test. A step test changes
the reference value of the currently selected control
mode, in line with the test waveform, to see how it takes
effect.