Figure. 5.4.27 - 130. Amplitude scaling to match the nominal currents and CTs in the differential relay.
Nominal current matching is only part of the differential protection settings. The vector group of the
transformer is also important, since the differential function is interested in the angle difference of the
measured current vectors. In this example the transformer's vector group is Yd1, which means that the
transformer's HV side is connected to the Y and the LV side to the delta. Therefore, the LV side is in
30-degree lag in relation to the HV side vectors.
The number '1' in the vector group's name comes from the angle in the phase current difference
between the HV and the LV side. If one imagines the HV side current's Y placed upside down on the
face of a clock (with the Y's leg pointing at 12), the LV side's delta would be pointing at 1. Likewise, '11'
means that the LV side is leading 30 degrees; '5' and '7' are just the other ends of the windings thus
causing a 180-degree difference between the '1' and '11' clock numbers.
The following example explains transformer current vectors and what a connection might look like.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
256
© Arcteq Relays Ltd
IM00001