Hot condition:
- Long heat T const (hot)
- Short heat T const (hot)
- Hot condition theta limit (Cold
→
Hot spot)
0.0…500.0 min, setting step 0.1 min
0.0…500.0 min, setting step 0.1 min
0.00…100.00 %, setting step 0.01 %
Reset (Cooling)
Reset ratio (pick-up and alarms)
99 %
Stop condition:
- Long cool T const (stop)
- Short cool T const (stop)
- Short cool T in use time
0.0…500.0 min, setting step 0.1 min
0.0…500.0 min, setting step 0.1 min
0.0…3000.0 min, setting step 0.1 min
Run condition:
- Long cool T const (stop)
0.0…500.0 min, setting step 0.1 min
Operation time
Definite time function operating time setting
0.0…3600.0 s, setting step 0.1 s
Inaccuracy:
- Pick-up and reset
±1.0 % or ±500 ms
Environmental settings
Thermal replica temperature estimates
Selectable between °C and °F
Ambient temperature effect
k min. and max. range
Ambient temperature min. and max. range
Linear or manually set curve
0.01...5.00 × I
N
, setting step 0.01 × I
N
–60…500 deg, setting step 1 deg
Thermal model biasing (ambient):
- Set ambient temperature
- RTD
–60…500 deg, setting step 1 deg
Used measured ambient value
10.2.1.15 Power protection (P, Q, S>/<; 32)
Table. 10.2.1.15 - 456. Technical data for the power protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Voltage inputs
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
(+ U
0
)
Calculated measurements
Three-phase active, reactive or apparent power (P, Q or S) value based on the chosen or
set nominal amplitude.
Pick-up
Comparator selection
> or <
> or <
-500.000...500.000 %/MVA
N
, setting step 0.005 %/MVA
N
Inaccuracy:
- Active, reactive, or apparent
power
Typically <1.0 %P
SET
Operation time
Definite time function operating
time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (P
M
/P
SET
ratio
1.05
→
)
±1.0 % or ±35 ms
Instant operation time
Start time and instant operation
time (trip):
- PQS
M
/PQS
SET
ratio 1.05
→
<40 ms
Genera
Generattor Commander
or Commander
Instruction manual