C-3
Setting Suppression Release Device and Point Types
Overview
This section describes how to set the device and point types required for suppression release
operation.
Device Types
Suppression release device types are shown in the table below.
Before assigning suppression release point types, make sure the appropriate device types have
been assigned to each NAC and device in each hazard area.
Refer to “Chapter 7. Programming Points” for general instructions on configuring device
Continued on next page
types.
Table C-1. Suppression Release Device Types
Class
Device Type
Application
NAC
SIGA
SIGB
Class A or Class B signal
(1&2, 3&4 in pairs)
LIFEalarm
HEAT
ION
PHOTO
XPHOTO
Detector
ADRPUL
Pull Station
Monitor
MAZAM
MBZAM
Class A or Class B Monitor ZAM
(T-sense)
IAM
Line Power IAM (T-sense)
Release
RELEASE
Agent Release Peripheral