10-17
Step 4. Edit An Output Statement’s Properties
Procedure
An output’s properties specify what occurs (for example, a limited set of strobes/horns
activate) when the Input Side of the CC Equation is True. Output Properties are set through the
Custom Control output dialog. Follow these steps to open this dialog.
1.
Highlight one of the equation’s output qualifiers and click the right mouse button. A menu
of choices appears.
2.
Click on Properties. A dialog similar to the following appears.
Figure 10-9. Custom Control Output Dialog
3.
Use Table 10-2 to set the Opcode and Qualifier.
Continued on next page
Table 10-2. Output Opcodes and Qualifiers
Opcode
Qualifier
Application
Hold
ON
When the input side of the equation is true, Hold ON turns the referenced
output point ON. The output remains ON until another equation turns the
output OFF or the system is reset. List L7 (Control Points, Off with Reset) is
useful for turning OFF a number of points simultaneously.
OFF
When the input side of the equation is true, Hold OFF turns the referenced
output point OFF. The output point remains OFF until another equation turns
the output point ON or the system is reset.