Monitor Point Types,
Continued
A-15
TROUBLE
Used for trouble monitoring only. No alarm is generated by this point type.
VSMOKE
Used with smoke detectors whose alarm status must be verified.
GVMON
Used when the abnormal condition of the circuit must be verified.
LATSUPV
Supervisory Monitor - latch until reset. Used for generic supervisory alarm.
STYLEC
Style-C Fire Alarm Monitor. Used when only current limited devices are connected to the
zone. A short circuit is reported as a Trouble.
Continued on next page
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Trouble Monitor
Abnormal
Open
Trouble Monitor
Open Trouble
Short
Trouble Monitor
Abnormal
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Smoke Detector
Verified Alarm
Open
Smoke Detector
Open Trouble
Short
Smoke Detector
Fire Alarm
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Fire Monitor
Verified Alarm
Open
Fire Monitor
Open Trouble
Short
Fire Monitor
Fire Alarm
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Supervisory Alarm
Abnormal
Open
Supervisory Alarm
Open Trouble
Short
Supervisory Alarm
Abnormal
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Fire Monitor Zone
Fire Alarm
Open
Fire Monitor Zone
Open Trouble
Short
Fire Monitor Zone
Short Trouble