C-5
Building and Configuring Hazard Areas
Overview
This section describes how to create and configure hazard areas. Building a hazard area
consists of assigning point types to the hazard area, at which point the programmer places each
point in its respective branch of the hazard area. Configuring a hazard area consists of setting
various options, from dual-detector operation to agent release delay durations.
Assigning Point Types
Table C-3, below, identifies the device and point types that apply to different components of
each hazard area.
Drag and drop the appropriate points from the Points list to the appropriate hazard area title.
The points will automatically be placed under the correct branches of the hazard area.
Notes:
•
Do not attempt to drag a point to a branch of a hazard area; simply drag it to the hazard
area title.
Continued on next page
•
To expand or collapse hazard area views, click the + or - icons next to each line.
Table C-3. Hazard Area Components
Component
Device Type
Point Type
AUTOMATIC
RELEASE
HEAT
ION
PHOTO
MAZAM
MBZAM
IAM
SUPDET
MANUAL RELEASE
MAZAM
MBZAM
ADRPUL
IAM
SUPDUMP
ABORT
MAZAM
MBZAM
IAM
SUPABRT
RELEASE
NOTIFICATION NACS
SIGA
SIGB
RELVIS
RELSIG
RELWVIS
RELISIG
RELEASE OUTPUT
SIGA
SIGB
RELEASE
SUPREL