![Ansul AutoPulse Z-28 Скачать руководство пользователя страница 177](http://html1.mh-extra.com/html/ansul/autopulse-z-28/autopulse-z-28_instructions-manual_2946331177.webp)
Addresses for Pseudo Points,
Continued
A-29
AUTOPULSE Z-28
User
Digital Pseudos
The user digital pseudo card in the AUTOPULSE Z-28 is at address 19. It has 75 points
available for specialized applications programming. Any point may be programmed as one of
the four types of digital pseudos (i.e. UTILITY, FIRE, etc.), and each may be assigned a 40-
character custom label.
Note that any user pseudo points defined as FIRE type are not auto-generated in the General
Alarm List (L1), and SUPERVISORY points are not generated into the Supervisory Monitor
List (L8).
Analog Pseudo Points
Analog pseudo points exist as counters or timers in the AUTOPULSE Z-28 system. SMPL
delay and cycle equations may be written referencing the user Analog pseudo points on the
output side (for delay/cycle operations). Each analog point may contain a value from 0-65,535
and the point is considered ON when the value is non-zero. For delay and cycle purposes, the
maximum allowable value gives a real-time range of just over 18 hours. There are two analog
pseudo cards in the AUTOPULSE Z-28 system - one reserved for system analogs, and one
reserved for user points.
AUTOPULSE Z-28
System Analog Pseudos
The AUTOPULSE Z-28 system has one analog pseudo card reserved for system use at address
20. It contains a total of 25 points. At present, only the first 12 are used, and the remainder are
Continued on next page
reserved for future expansion.
Point
Type
Label
Description
D53
R U
RS232 Port B
Disconnected
On whenever nothing is connected to Port B on
the RS232 or RS232/Modem card.
D54-
D57
-
Reserved
System
Pseudo Point
unused
D58
R U
Network
System Reset
Used in 4120 Network programming to perform
an AUTOPULSE Z-28 System Reset from
another node.
D59
R U
Network Signal
Silence
Used in 4120 Network programming to perform
an AUTOPULSE Z-28 Alarm Silence from
another node.
D60
-
Digital: P60
unused
D75
- Digital:
P75
unused
Table A-13. Digital Pseudo Points
, continued