Programming a Point’s Software Point Type,
Continued
7-9
Continued on next page
Table 7-3. Point Types
Category
Point Type
Application
Monitor
ABORT
Abort zone (pre-signal)
DAMPER
Damper Monitor (open/closed)
DUCT
Duct Detector
EMERG
Combination Fire/Emergency Alarm
FIRE
Fire Alarm (Generic)
FLAME
Flame Detector
FPUMP
Fire Pump Monitor
GENMON
Generator Monitor
GVMON
Generic verified Monitor
HEAT
Heat Detector
LATSUPV
Latching Supervisory
PULL
Manual Pull Station
S2STAGE
2-stage Monitor (abn=presignal; short=alarm)
SDUCT
Supervisory Duct Detector
SFIRE
Combination Smoke Fire Zone
SFPUMP
Supervisory Fire Pump Monitor
SGENMON
Supervisory Generator Monitor
SMOKE
Smoke detector
SO
Sprinkler supervisory (normally open)
SPULL
Combination Smoke/Pull Zone
STYLEC
Style -C Monitor Point (current limit=fire alarm;
short/open=trouble)
SUPABRT
Suppression release abort zone
SUPDET
Suppression release detector zone
SUPDUMP
Suppression release manual dump
SUPPRES
Suppression release pressure monitor
SUPV
Supervisory (generic)
TROUBLE
Trouble Monitor
UTILITY
Non-alarm utility with Tri-state ability
VSFIRE
Verified Smoke/Fire Zone
VSMOKE
Verified Smoke Zone
VSPULL
Verified combination Smoke/Pull Zone
WATER
Waterflow Switch
WSO
Waterflow Switch/Sprinkler supervision (Normally
Open)