Setting Suppression Release Device and Point Types,
Continued
C-4
Point Types
Table C-2 summarizes the point types that must be assigned to each device type in a hazard
area.
Assign point types as shown in Chapter 7 to the applicable device types.
Note: List points L9 through L12 (suppression lists) are not used in version 3.x of the pro-
grammer.
Table C-2. Suppression Release Point Types
Device Type
Point Type
Application
SIGA
SIGB
RELSIG
Suppression release audible signal
(Temporal on first alarm; 120 bpm on
hazard alarm (delay timers active);
steady on release; off on silence).
RELVIS
Suppression release visual signal (on
when releasing output activates; off on
reset).
RELWVIS
Releasing warning visual circuit (on when
alarm occurs in hazard area; off on
reset).
RELISIG
Releasing investigation signal (NYC
abort operation).
SUPREL
Suppression release power
SIGNAL
Generic output (custom control must be
written to control the device).
HEAT
ION
PHOTO
MAZAM
MBZAM
IAM
SUPDET
Suppression release detect zone
MAZAM
MBZAM
ADRPUL
IAM
SUPDUMP
Suppression release manual dump
MAZAM
MBZAM
IAM
SUPABRT
Suppression release abort zone
SUPPRESS
Suppression release pressure monitor
RELEASE
SUPREL
Suppression release output
SIGNAL
Generic output (custom control must be
written to control the device).