Enabling System Options,
Continued
5-5
Alarm Cutout Timer
The Alarm Signal Cutout timer allows you to set a duration for how long signals sound after an
alarm. In other words, when an alarm condition exists, the signals sound until silenced. With
this option set at two minutes, building signals sound on alarm for two minutes and then stop
sounding. However, the alarm condition remains active in the panel. The default setting for
this options is No Cutout (meaning an Alarm Silence is required to shut off signals).
Enable this option by selecting the check box shown below. Refer to Figure 5-2 for the
location of this option.
Figure 5-6. Alarm Cutout Timer Option
Door Drop on Alarm
The Door Drop on Alarm timer allows the AUTOPULSE Z-28 to hold doors open for a set
duration during an alarm condition. After that duration has expired, the AUTOPULSE Z-28
shuts off the door holder relays and the doors close. The range for the timer is 0-60 seconds
with a default setting of zero seconds. To have door holders drop the doors immediately, leave
the timer set to zero seconds.
Enable this option by selecting the check box shown below. Refer to Figure 5-2 for the location
of this option.
Figure 5-7. Door Drop on Alarm Option
Door Drop on AC Fail
The Door Holder - AC Fail Door Drop Timer allows the AUTOPULSE Z-28 to hold doors
open for a set duration during an AC power loss condition. After that duration has expired, the
AUTOPULSE Z-28 shuts off the door holder devices and the doors close. The range for the
timer is 0-60 minutes, with a default setting of 5 minutes. To have door holders drop the doors
immediately upon AC power loss, set the timer to zero minutes.
Enable this option by selecting the check box shown below. Refer to Figure 5-2 for the
location of this option.
Figure 5-8. Door Drop on AC Fail Option