Monitor Point Types,
Continued
A-10
FLAME
Used for flame detectors.
PULL
Used with manual pull stations.
SMOKE
Used with 2- and 4-wire smoke detectors.
EMERG
Use for an emergency monitor zone in which two types of alarm devices - for example,
emergency alarm devices such as Nurse Call and fire alarm devices -- are connected to an IAM
or ZAM. Emergency devices require the use of a current limiting resistor. These devices
generate an Emergency Alarm condition at the panel.
Continued on next page
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Flame Detector
Fire Alarm
Open
Flame Detector
Open Trouble
Short
Flame Detector
Fire Alarm
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Manual Pull Station
Fire Alarm
Open
Manual Pull Station
Open Trouble
Short
Manual Pull Station
Fire Alarm
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Smoke Detector
Fire Alarm
Open
Smoke Detector
Open Trouble
Short
Smoke Detector
Fire Alarm
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Monitor Zone
Emergency Alarm
Open
Monitor Zone
Open Trouble
Short
Monitor Zone
Fire Alarm