Addresses for Pseudo Points,
Continued
A-31
List Pseudo Points
List pseudo points provide a convenient way to group points in any manner the user desires.
The AUTOPULSE Z-28 contains two list pseudo cards - one reserved for the system and one
for the user. The list status is determined by counts which are maintained for the following
states:
•
Fire Count
•
Trouble Count
•
Supervisory Count
•
Normal
•
Open
•
Limited
•
Short
•
Fire Ack
•
Trouble Ack
•
Supervisory Ack
•
Disable
•
On/Input
•
On/Coding
•
Manual Control
The AUTOPULSE Z-28 restricts the total number of points in any one list to 255. It also
restricts the total number of points available on any one list card to 500 (the total number of
points in all lists on one list card cannot exceed 500).
AUTOPULSE Z-28
System Lists
The AUTOPULSE Z-28 system reserves one list card at address 22 for system use. Currently,
12 of the 25 system lists are used by the AUTOPULSE Z-28 application. All of these lists
control application-specific operation of the AUTOPULSE Z-28 panel. Some are auto-
generated by the system as points are added and may not be edited, while the remainder are
filled by the user to activate pre-defined applications. The system lists are shown below.
Continued on next page
Table A-15. System Lists
Point
Label
Description
L1
General Alarm
Monitor Points
Auto-generated by the panel and not editable. Contains all
fire-alarm monitor points in the system plus the Manual
Evac pseudo. User FIRE digital pseudos are not auto-
generated here.
L2
Waterflow Alarm
Monitor Zones
Auto-generated by the panel and not editable. Contains all
waterflow-type monitor points (WSO)
L3
Sprinkler
Supervisory
Monitor Zones
Auto-generated by the panel and not editable. Contains all
sprinkler-type monitor points (SO)
L4
Primary Elevator
Recall Monitors
Filled by the user. When in fire state, will activate the
primary elevator recall function.
L5
Alternate Elevator
Recall Monitors
Filled by the user. When in fire state, will activate the
alternate elevator recall function.