6-37
Programming an LCD Annunciator Card,
Continued
Step 2. Programming
LEDs
The LCD Annuciator contains LEDs that can be used to monitor the state of a point,
illuminating a specific color when the state of the point is equal to a specific condition.
1.
Click on the Device Type field corresponding to the LED that you want to program and
choose Multicolor.
2.
Click on the Point Type field and choose one of the following. Note that LED1 and LED2
illuminate Yellow or Red, whereas LED3 illuminates either Yellow or Green.
3.
Click on the Mode drop down list box. Choose the mode (State) that must be true to
illuminate the LED. Refer to the following table for details on the available modes.
Continued on next page
Table 6-14. LED Point Types
LED
Available Point Types
LED 1
Select Yellow for a Yellow LED
Select Non Yellow for a Red LED
LED 2
Select Yellow for a Yellow LED
Select Non Yellow for a Red LED
LED 3
Select Yellow for a Yellow LED
Select Non Yellow for a Green LED
Table 6-15. Modes for User-Defined LEDs
Mode
Meaning
Disable
LED illuminates when state of REF ADDR (point) is DISABLED.
Fire
LED illuminates when state of REF ADDR (point) goes into ALARM
LF
LED illuminates when ALARM ACK button on the panel is pushed.
LS
LED illuminates when SUPV ACK button on the panel is pushed.
LT
LED illuminates when TROUBLE ACK button on the panel is
pushed.
OFF
LED illuminates when the state of the REF ADDR (point) is OFF.
ON
LED illuminates when the state of the REF ADDR (point) is ON
SMPL
LED illuminates when the state of a Custom Control equation(s) is
TRUE.
SUPERV
LED illuminates when the state of the REF ADDR (point) goes into
SUPERV.
TROUBLE
LED illuminates when the state of the REF ADDR (point) goes into
ALARM.