Monitor the signal ALARM until it appears on the corresponding binary output or
on the local HMI.
5.
Compare the measured temperature with the setting.
6.
Measure the LFPTTR/LCPTTR (26)protection trip time.
Use the TRIP signal from the configured binary output to stop the timer.
7.
Take the TEMP readings.
Compare with the setting of
TripTemp
.
8.
Activate the BLOCK binary input.
The signals ALARM, RI and TRIP should disappear.
9.
Reset the BLOCK binary input.
10. Check the reset limit (TdReset).
Monitor the signal PICKUP until it disappears on the corresponding binary output
or on the local HMI, take the TEMP readings and compare with the setting of
ReclTemp
.
11. Compare the measured trip time with the setting according to the formula.
12. Reset the thermal memory.
13. Continue to test another function or end the test by changing the test mode setting
to
Disabled
.
6.4.8.2
Completing the test
Continue to test another function or end the testing by setting the parameter
TestMode
to
Disabled
under
Main menu/Tests/IED test mode/1:TESTMODE
. If another
function is tested, then set the parameter
Blocked
to
No
under
Main menu/Tests/
Function test modes/Current/LFPTTR(26,T>)/1:LFPTTR
,
Main menu/Tests/
Function test modes/Current/LCPTTR(26,T>)/1:LCPTTR
for the function, or for
each individual function in a chain, to be tested next. Remember to set the parameter
Blocked
to
Yes
, for each individual function that has been tested.
6.4.9
Breaker failure protection, phase segregated activation and
output CCRBRF (50BF)
Prepare the IED for verification of settings as outlined in
.
Values of the logical signals for CCRBRF (50BF) are available on the local HMI under
Main menu/Tests/Function status/Current/CCRBRF(50BF)/1:CCRBRF
. The
Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
The Breaker failure protection, 3-phase activation and output function CCRBRF
(50BF) should normally be tested in conjunction with some other function that
provides an initiate signal. An external INITIATE signal can also be used.
1MRK 506 331-UUS A
Section 6
Testing functionality
75
Commissioning Manual
Содержание Relion 650 Series REL650
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 22: ...14 ...
Страница 44: ...36 ...
Страница 52: ...44 ...
Страница 156: ...148 ...
Страница 166: ...158 ...
Страница 175: ...167 ...