X1
R
X
85%
1
3
5
2
6
4
50% RLdFwd
ArgNegRes
0.5·RFltFwdPP
LdAngle
ANSI09000735-1-en.vsd
ArgDir
60°
)
/
(
phase
W
)
/
(
phase
W
7
ANSI09000735 V1 EN
Figure 14:
Operating characteristic for phase selection function, forward direction
phase-to-phase faults
Table 7:
Test points for phase-to-phase loops A-B (Ohm/phase)
Test point
Reach
Value
Comments
1
X
X1
R
0
2
X
0
R
RLdFwd
When RLdFWd < 0,5·RFLdFwPP
R
0.5·RFLdFwPP
When RLdFwd > 0,5·RFLdFwPP
3
X
0.85·X1
R=0.491·X1+0.5 RFLdFwdPP
R
0.85·X1·1/tan(60°)+0.5
RFLdFwdPP
4
X
0.85·X1
Can be limited by RFLdFwPP
R
-0.85·X1·tan (AngNegRes-90°)
5
X
0.5·RFLdFwdPP·tan (ArgLd)
Only when RLdFwd < RFLdFwPP
R
0.5·RFLdFwdPP
6
X
-0.5·RLdFwd·tan (ArgDir)
R
0.5·RLdFwd
Section 6
1MRK 506 331-UUS A
Testing functionality
54
Commissioning Manual