Checking the case with fault current below set value
Pickup_BlkCont
The case shall simulate a case where the fault current is very low and operation will
depend on CB position signal from CB auxiliary contact. It is suggested that re-trip
without current check is used, setting
RetripMode
=
No CBPos Check
.
1.
Set
FunctionMode
=
Current&Contact
.
2.
Apply input signal for CB closed to relevant input or inputs 52a_A (B or C)
3.
Apply the fault condition with input signal(s) for initiation of CCRBRF (50BF).
The value of current should be below the set value
Pickup_BlkCont
4.
Verify that phase selection re-trip (if selected) and back-up trip are achieved after
set times. Failure to trip is simulated by keeping the signal(s) CB closed activated.
5.
Disconnect the AC and the INITIATE signal(s). Keep the CB closed signal(s).
6.
Apply the fault and the initiation again. The value of current should be below the
set value
Pickup_BlkCont
.
7.
Arrange disconnection of BC closed signal(s) well before set back-up trip time
t2
.
It simulates a correct CB tripping.
8.
Verify that back-up trip is not achieved. Re-trip can appear for example, due to
selection “Re-trip without current check”.
9.
Disconnect injected AC and INITIATE input signals.
6.4.9.8
Completing the test
Continue to test another function or end the testing by setting the parameter
TestMode
to
Disabled
under
Main menu/Tests/IED test mode/1:TESTMODE
. If another
function is tested, then set the parameter
Blocked
to
No
under
Main menu/Tests/
Function test modes/Current/CCRBRF(50BF)/X:CCRBRF
for the function, or for
each individual function in a chain, to be tested next. Remember to set the parameter
Blocked
to
Yes
, for each individual function that has been tested.
6.4.10
Breaker failure protection, phase segregated activation and
output CSPRBRF (50BF)
Prepare the IED for verification of settings as outlined in
Values of the logical signals for CSPRBRF (50BF) are available on the local HMI
under
Main menu/Tests/Function status/Current/CSPRBRF(50BF)/1:CSPRBRF
.
The Signal Monitoring in PCM600 shows the same signals that are available on the
local HMI.
Breaker failure protection, phase segregated activation and output CSPRBRF
(50BF)should normally be tested in conjunction with some other function that provides
an initiate signal. An external INITATE signal can also be used.
Section 6
1MRK 506 331-UUS A
Testing functionality
80
Commissioning Manual
Содержание Relion 650 Series REL650
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 22: ...14 ...
Страница 44: ...36 ...
Страница 52: ...44 ...
Страница 156: ...148 ...
Страница 166: ...158 ...
Страница 175: ...167 ...