Note that the time synchronization source has to be activated.
Otherwise the value is always
Normal
.
8.1.4
Running the display test
To run the display test, either use the push buttons or start the test via the menu.
•
Select
Main menu/Tests/LED test
.
•
Press simultaneously
and
.
All the LEDs are tested by turning them on simultaneously. The display shows a
set of patterns so that all the pixels are activated. After the test, the display returns
to normal state.
8.2
Indication messages
8.2.1
Internal faults
When the Ready LED indicates an internal fault by flashing, the message associated
with the fault is found in the internal event list in the LHMI menu
Main menu/
Diagnostics/Internal events
. The message includes the date, time, description and
signal state for the fault. The internal event list is not updated dynamically. The list is
updated by leaving the
Internal events
menu and then selecting it again. The current
status of the internal fault signals can also be checked via the LHMI in
Main menu/
Diagnostics/IED status
.
Different actions are taken depending on the severity of the fault. If the fault is found
to be permanent, the IED stays in internal fault mode. The IED continues to perform
internal tests during the fault situation.
When a fault appears, the fault indication message is to be recorded and stated when
requesting support or service.
1MRK 506 331-UUS A
Section 8
Troubleshooting
151
Commissioning Manual
Содержание Relion 650 Series REL650
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 22: ...14 ...
Страница 44: ...36 ...
Страница 52: ...44 ...
Страница 156: ...148 ...
Страница 166: ...158 ...
Страница 175: ...167 ...