Values of the logical signals for BRCPTOC (46) are available on the local HMI under
Main menu/Tests/Function status/Current/BRCPTOC(46,lub)/X:BRCPTOC
. The
Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
6.4.13.1
Measuring the operate and time limit of set values
1.
Check that the input logical signal BLOCK to the BRCPTOC (46) function block
is logical zero and note on the local HMI that the output signal TRIP from the
BRCPTOC (46) function block is equal to the logical 0.
2.
Set the measured current (fault current) in one phase to about 110% of the set
operating current
IP>
.
Observe to not exceed the maximum permitted overloading of the current circuits
in the terminal.
3.
Switch on the fault current and measure the operating time of BRCPTOC (46).
TRIP is controlled by Gate 13 in the configuration.
Use the TRIP signal from the configured binary output to stop the timer.
4.
Compare the measured time with the set value
tOper
.
5.
Activate the BLOCK binary input.
6.
Switch on the fault current (110% of the setting) and wait longer than the set
value
tOper
.
No TRIP signal should appear.
7.
Switch off the fault current.
8.
Set the measured current (fault current) in same phase to about 90% of the set
operating current
IP>
. Switch off the current.
9.
Switch on the fault current and wait longer than the set value
tOper
.
No TRIP signal should appear.
10. Switch off the fault current.
6.4.13.2
Completing the test
Continue to test another function or end the testing by setting the parameter
TestMode
to
Disabled
under
Main menu/Tests/IED test mode/1:TESTMODE
. If another
function is tested, then set the parameter
Blocked
to
No
under
Main menu/Tests/
Function test modes/Current/BRCPTOC(46,lub)/X:BRCPTOC
for the function, or
for each individual function in a chain, to be tested next. Remember to set the
parameter
Blocked
to
Yes
, for each individual function that has been tested.
6.4.14
Directional underpower protection GUPPDUP (37)
Prepare the IED for verification of settings as outlined in
.
1MRK 506 331-UUS A
Section 6
Testing functionality
87
Commissioning Manual
Содержание Relion 650 Series REL650
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 22: ...14 ...
Страница 44: ...36 ...
Страница 52: ...44 ...
Страница 156: ...148 ...
Страница 166: ...158 ...
Страница 175: ...167 ...