or for each individual function in a chain, to be tested next. Remember to set the
parameter
Blocked
to
Yes
, for each individual function that has been tested.
6.3.2
Phase selection with load encroachment, quadrilateral
characteristic FDPSPDIS (21)
Prepare the IED for verification of settings as outlined in
Values of the logical signals for FDPSPDIS are available on the local HMI under
Main menu/Tests/Function status/Impedance/FDPSPDIS/1:FDPSPDIS
. The
Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
The phase selectors operate on the same measuring principles as the impedance
measuring zones. So it is necessary to follow the same principles as for distance
protection, when performing the secondary injection tests.
Measure operating characteristics during constant current conditions. Keep the
measured current as close as possible to the rated value of its associated input
transformer, or lower. But ensure that it is higher than the set minimum operating current.
Ensure that the maximum continuous current to the IED does not exceed four times its
rated value, if the measurement of the operating characteristics runs under constant
voltage conditions.
To verify the settings the operating points according to figures
should be
Section 6
1MRK 506 331-UUS A
Testing functionality
52
Commissioning Manual