Section 6
Testing functionality
6.1
Testing disturbance report
6.1.1
Introduction
The following sub-functions are included in the disturbance report function:
•
Disturbance recorder
•
Event list
•
Event recorder
•
Fault locator
•
Trip value recorder
•
Indications
If the disturbance report is enabled, then its sub-functions are also set up and so it is
not possible to only disable these sub-functions. The disturbance report function is
disabled (parameter
Operation
=
Disabled
) in PCM600 or the local HMI under
Main
menu/Settings/IED Settings/Monitoring/Disturbance report/1:DRPRDRE
.
6.1.2
Disturbance report settings
When the IED is in test mode, the disturbance report can be made active or inactive. If
the disturbance recorder is turned on during test mode, recordings will be made. When
test mode is switched off all recordings made during the test session are cleared.
Setting
OpModeTest
for the control of the disturbance recorder during test mode are
located on the local HMI under
Main menu/Settings/IED Settings/Monitoring/
Disturbance report/1:DRPRDRE
.
6.2
Identifying the function to test in the technical
reference manual
Use the technical manual to identify function blocks, logic diagrams, input and output
signals, setting parameters and technical data.
1MRK 506 331-UUS A
Section 6
Testing functionality
45
Commissioning Manual
Содержание Relion 650 Series REL650
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 22: ...14 ...
Страница 44: ...36 ...
Страница 52: ...44 ...
Страница 156: ...148 ...
Страница 166: ...158 ...
Страница 175: ...167 ...