90 Program features
needs to be enabled or disabled based on the motor control mode and the nominal
current as follows:
• With the vector control, the motor phase loss detection is always on and there are
no operational limits.
• With the scalar control, the motor phase loss detection activates when the motor
frequency is above 10% of the motor nominal frequency. This limit cannot be
changed.
With motors having nominal current below 1/6 of drive nominal current, the
supervision must be disabled as the drive cannot measure the motor current
accurately.
Safe torque off detection (parameter
)
The drive monitors the status of the Safe torque off input, and this parameter selects
which indications are given when the signals are lost. (The parameter does not affect
the operation of the Safe torque off function itself). For more information on the Safe
torque off function, see chapter
Planning the electrical installation
, section
Implementing the Safe torque off function
in the
Hardware manual
of the drive.
Swapped supply and motor cabling (parameter
)
The drive can detect if the supply and motor cables have accidentally been swapped
(for example, if the supply is connected to the motor connection of the drive). The
parameter selects if a fault is generated or not.
Current limit function (parameters
, and
)
The drive monitors the maximum current limit, its related parameters and helps the
motor not to reach its stall current limit. The maximum current, monitoring time, and
how the drive should react to these conditions can be set in the parameters
,
,
and
respectively
.
By default, when the drive reaches the maximum current limit and exceeds the
monitor time, a warning message (
) is displayed.
Stall function (parameters
…
)
The drive monitors the stall current limit, its related parameters and helps to prevent
stalling of the motor. You can adjust the supervision limits (current, frequency and
time) and choose how the drive reacts to a stall condition.
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...