132 Control macros
Default control connections for the PFC macro
Terminal sizes
• (frames R0…R8): 0.14…1.5 mm
2
(all terminals)
• Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Max.
500 ohm
1…10 kohm
X1
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
PID setpoint, 0…10 V
1) 5)
:
3
AGND
Analog input circuit, common
4
+10V
10 V DC reference voltage
5
AI2
PID feedback, 4...20mA
1) 5)
: see
6
AGND
Analog input circuit, common
7
AO1
Output frequency: 0…20 mA
6)
: see
8
AO2
Motor current, 0…20 mA
6)
: see
9
AGND
Analog output circuit common
X2, X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 VDC, max. 250 mA
4)
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1) (EXT 1)
5)
:
see
14
DI2
Run enable
(if 0, drive stops)
5)
:
see
15
DI3
EXT1 (0) / EXT 2 (1)
5)
: see
16
DI4
Not configured
17
DI5
Not configured
18
DI6
Not configured
X6,X7, X8 Relay outputs
19
RO1C
Running
6)
: see
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Fault (-1)
6)
:
see
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
PFC2 (the 2nd motor = the first auxiliary
motor)
6)
: see
250 V AC / 30 V DC
26
RO3A
27
RO3B
X5
Built-in fieldbus
29
B+
Internal Modbus RTU (EIA-485). See
control through the embedded fieldbus interface
30
A-
31
DGND
(Frame R0...R2)
S100
TERM&BIAS
Termination resistor and bias resistor switch
(Frame R3...R8)
S100
TERM
Termination resistor switch
S200
BIAS
Bias resistor switch
X4
Safety torque off
R0...R2 R3...R
33
-
OUT1
Safety torque off function. Factory connection.
Both circuits must be closed for the drive to start.
See
Safe torque off function
in the drive
hardware
manual.
34
SGND
OUT2
35
OUT1 SGND
36
IN1
IN1
37
IN2
IN2
X10
24 V AC/DC (frames R6...R8 only)
40
24 V AC/DC- in 24V AC/DC input, for control unit power supply
when external main power is disconnected.
41
24 V AC/DC+ in
X11
Redundant auxiliary voltage output (frames R0...R2)
42
+24 V
Aux. voltage 24 V DC, max. 250 mA
4)
43
DGND
Aux. voltage output common
44
DCOM
Digital input common for all
3)
R3...R8
3)
3)
2)
7)
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...