354 Parameters
Specifies hardware-related options that require differentiated
parameter defaults.
This parameter is not affected by a parameter restore.
0b0000
0b0000…0b1111
Hardware options configuration word.
1 = 1
Specifies more hardware-related options that require
differentiated parameter defaults. See parameter
.
WARNING!
An incorrect setting may cause the motor
to rush uncontrollably, or the brake chopper or resistor
to overload.
0b0000
0b0000…0b1111
Hardware options configuration word.
1 = 1
Selects the fan control type. The fan control functionality
enables heat dissipation from the drive and avoids dust
accumulation in the drive.
Auto
Controls the fan automatically according to the temperature
changes of the drive.
0
Always on
Fan runs continuously with the maximum speed (50Hz).
1
96
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection.
Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the
Drive composer PC tool. (Those are specified under
View
–
Settings
–
Drive default language
.)
Not selected
Not selected
None.
0
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Value
0
Supply frequency
60 Hz
If you change the value of this bit, you have to do a complete reset to
the drive after the change. After reset you have to reselect the macro
to be used.
See section
Differences in the default values between 50 Hz and
60 Hz supply frequency settings
on page
.0 = 50 Hz.
1 = 60 Hz.
1…12
Reserved
13
du/dt filter
activation
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
14…15 Reserved
Bit
Name
Value
0...4
Reserved
5
Bypass present
1 = Bypass is used.
6
Cabinet drive
0 = Inactive, 1 = Active. Only for drive frames R6 or larger.
7
Reserved
0 = Inactive, 1 = Active. Only for drive frames R6 or larger.
8...15
Reserved
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...