436 Fault tracing
000D (Permanent magnet motors
only)
Second acceleration did not
finish within reasonable time.
Contact your local ABB representative.
000E…0010 Internal error.
Contact your local ABB representative.
0011 (Synchronous reluctance
motors only)
Pulse test error.
Contact your local ABB representative.
0012 Motor too large for advanced
standstill ID run.
Check that the motor and drive sizes are
compatible.
Contact your local ABB representative.
0013 (Asynchronous motors only)
Motor data error.
Check that the motor nominal value
settings in the drive are the same as in
the motor nameplate.
Contact your local ABB representative.
FF63
STO diagnostics
failure.
SW internal malfunction.
Reboot the control unit (using parameter
or by cycling
power.
FF81
FB A force trip
A fault trip command has been
received through fieldbus
adapter A.
Check the fault information provided by
the PLC.
FF8E
EFB force trip
A fault trip command has been
received through the
embedded fieldbus interface.
Check the fault information provided by
the PLC.
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...