Parameters 301
DI6
Digital input DI6 (
, bit 5).
7
Timed function 1
Bit 0 of
18
Timed function 2
Bit 1 of
19
Timed function 3
Bit 2 of
20
Supervision 1
Bit 0 of
(see page
21
Supervision 2
Bit 1 of
(see page
22
Supervision 3
Bit 2 of
(see page
23
). -
Inverts the input of the process PID controller.
0 = Deviation not inverted (Deviation = Setpoint - Feedback)
1 = Deviation inverted (Deviation = Feedback - Setpoint)
See also section
Sleep and boost functions for process PID
Not inverted
(Ref - Fbk)
0.
0
Inverted (Fbk - Ref) 1.
1
). -
Defines the gain for the process PID controller. See
parameter
.
1.00
0.01…100.00
Gain for PID controller.
100 = 1
Defines the integration time for the process PID controller.
This time needs to be set to the same order of magnitude as
the reaction time of the process being controlled, otherwise
instability will result.
Note:
Setting this value to 0 disables the “I” part, turning the
PID controller into a PD controller.
60.0 s
0.0…9999.0 s
Integration time.
1 = 1 s
No.
Name/Value
Description
Def/FbEq16
Ti
O
I
G × I
G × I
I = controller input (error)
O = controller output
G = gain
Ti = integration time
Time
Error/Controller output
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...