286 Parameters
Ni1000
Ni1000 sensor connected to the analog input selected by
parameter
and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
16
PTC analog I/O
PTC sensor connected to analog input selected by parameter
and an analog output.
The required settings are the same as with selection
Note: With this selection, the control program converts the
analog signal to PTC resistance value in ohms and shows it
in parameter
The parameter name and unit still refer to
temperature.
20
PTC AI/DI Voltage
Divider tree
PTC sensor connected to the analog input selected by
parameter
. A special voltage
divider connection must be in use instead of the normal PTC
connection. The voltage divider connection uses the
ter10 V, digital input and analog input. See the drive
hardware manual for the actual connection.
This selection makes it possible to connect the PTC when no
analog output is available.
The required settings are same as with selection
Notes:
• Make sure that the digital input that you connect to this
voltage divider circuit is not used for any other purpose in
the control program.
• With this selection, the parameter
shows PTC
resistance in ohms, not motor temperature even the
parameter name and unit still refer to temperature.
23
Defines the fault limit for temperature supervision function 2.
When measured temperature 1 exceeds the limit, the drive
trips on fault
.
The unit is selected by parameter
.
130 °C or
266 °For
4500 ohm
-60…5000 °C or
-76…9032 °F or
0...5000 ohm
Fault limit for temperature monitoring function 2.
Note:
If the measured temperature source selection (
is PTC analog I/O or PTC AI/DI Voltage divider tree, the
motor thermal protection function converts the analog input
signal (
) to PTC resistance value (ohms). Also this limit
is then a resistance value even the parameter name and unit
refer to motor temperature (°C or °F). You cannot change the
unit to ohm by the time being (
1 = 1 unit
No.
Name/Value
Description
Def/FbEq16
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...