192 Parameters
mA
Milliamperes.
10
Defines the filter time constant for analog input AI2. See
parameter
0.100 s
0.000…30.000 s
Filter time constant.
1000 = 1 s
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
4.000 mA
0.000…22.000
Minimum value of AI2.
1000 = 1 unit
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
20.000 mA
0.000…22.000 mA
Maximum value of AI2.
1000 = 1 unit
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
.
(Changing the polarity settings of
can
effectively invert the analog input.)
0.000
-32768.000…
32767.000
Real value corresponding to minimum AI2 value.
1 = 1
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
.
See the drawing at parameter of
50.000
-32768.000…
32767.000
Real value corresponding to maximum AI2 value.
1 = 1
Value of analog input AI1 in percent of AI1 scaling (
-
).
0
0.00…100.00%
AI1 value
100 = 1%
Value of analog input AI2 in percent of AI2 scaling (
-
).
0
0.00…100.00%
AI2 value
100 = 1%
No.
Name/Value
Description
Def/FbEq16
AI
in
AI
scaled
)
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...