362 Parameters
Defines the level of flux braking power. (Other stopping and
braking modes can be configured in parameter group
Note:
This is an expert level parameter and should not be
adjusted without appropriate skill.
Disabled
Flux braking is disabled.
0
Moderate
Flux level is limited during the braking. Deceleration time is
longer compared to full braking.
1
Full
Maximum braking power. Almost all available current is used
to convert the mechanical braking energy to thermal energy
in the motor.
WARNING!
Using full flux braking heats up the motor
especially in cyclic operation. Make sure that the
motor can withstand this if you have a cyclic
application.
2
As a rule of thumb, define a level to which the output torque
must rise with minimum delay. This will increase the motor
current and improve the torque response at low speeds.
0.0
0.0...1600.0%
Optimizer torque limit.
10 = 1%
No.
Name/Value
Description
Def/FbEq16
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...