Program features 51
The drive contains two complete set of process PID controller settings that can be
used in place of the other as and when required. See parameter
.
Note:
Process PID control is available only in external control location EXT2. See
section
Local control vs. external control
(page
).
Quick configuration of the process PID controller
1. Activate the process PID controller:
Menu - Primary settings - PID - PID
controls
2. Select a feedback source:
Menu - Primary settings - PID - Feedback
3. Select a setpoint source:
Menu - Primary settings - PID - Setpoint
4. Set the gain, integration time, derivation time:
Menu - Primary settings - PID -
Tuning
5. Set the PID output limits:
Menu - Primary settings - PID - PID output
6. Select the PID controller output as the source of, for example,
22.11 Ext1 speed ref1:
Menu - Primary settings - Start, stop, reference -
Reference from
Process
PID
AI1
Process
actual
values
AI2
• • •
FBA
Setpoint
Speed, torque or
frequency
reference chain
Filter
Limitation
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...