320 Parameters
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used to
define deceleration ramp rate (see parameter group
). The frequency acceleration and
deceleration ramp times are therefore related to this value
(
not
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in e.g. fieldbus communication.
50.00 Hz
0.10…1000.00 Hz
Acceleration/deceleration terminal/initial frequency.
10 = 1 Hz
Defines the 16-bit scaling of torque parameters. The value of
this parameter (in percent of nominal motor torque)
corresponds to 10000 in e.g. fieldbus communication.
100.0%
0.1…1000.0%
Torque corresponding to 10000 on fieldbus.
10 = 1%
Defines the output power value that corresponds to 10000 in
e.g. fieldbus communication. The unit is selected by
parameter
.
1000.00 kW
0.10 …30000.00
kW or hp
Power corresponding to 10000 on fieldbus.
1 = 1 unit
Defines the 16-bit scaling of current parameters. The value of
this parameter corresponds to 10000 in fieldbus
communication.
10000 A
0…30000 A
Defines a speed corresponding to a zero reference received
from fieldbus (either the embedded fieldbus interface, or
interface FBA A). For example, with a setting of 500, the
fieldbus reference range of 0…20000 would correspond to a
speed of 500…[
] rpm.
Note:
This parameter is effective only with the ABB Drives
communication profile.
0.00 rpm
0.00 … 30000.00
rpm
Speed corresponding to minimum fieldbus reference.
1 = 1 rpm
Defines a frequency corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example, with a
setting of 30, the fieldbus reference range of 0…20000 would
correspond to a speed of 30…[
] Hz.
Note:
This parameter is effective only with the ABB Drives
communication profile.
0.00 Hz
0.00 … 1000.00 Hz Speed corresponding to minimum fieldbus reference.
10 = 1 Hz
Defines a filter time for signals
.
500 ms
2…20000 ms
Motor speed signal filter time.
1 = 1 ms
Defines a filter time for signal
.
500 ms
2…20000 ms
Output frequency signal filter time.
1 = 1 ms
Defines a filter time for signal
.
100 ms
2…20000 ms
Motor torque signal filter time.
1 = 1 ms
Defines a filter time for signal
.
100 ms
2…20000 ms
Output power signal filter time.
1 = 1 ms
No.
Name/Value
Description
Def/FbEq16
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...