Program features 41
Control interfaces
Programmable analog inputs
The control unit has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V) or current (0/4…20 mA) input by a switch
on the control unit, or with parameters. Each input can be filtered, inverted and
scaled.
Settings
(page
Programmable analog outputs
The control unit has two current (0…20 mA) analog outputs. Analog output 1 can be
set as a voltage (0/2…10 V) or current (0/4…20 mA) output by a switch on the control
unit, or with a parameter. Analog output 2 always uses current. Each output can be
filtered, inverted and scaled.
Settings
(page
Programmable digital inputs and outputs
The control unit has six digital inputs.
Digital input DI5 can be used as a frequency input or digital input.
Settings
Parameter groups
(page
(page
Programmable relay outputs
The control unit has three relay outputs. The signal to be indicated by the outputs can
be selected by parameters.
Settings
).
Fieldbus control
The drive can be connected to several different automation systems through its
fieldbus interfaces. See chapters
Fieldbus control through the embedded fieldbus
(page
) and
Fieldbus control through a fieldbus adapter
(page
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...