422 Fault tracing
A985
External warning 5
(Editable message text)
Programmable warning:
Fault in external device 5.
Check the external device.
Check setting of parameter
.
A991
Safe motor
temperature
You have configured a season
which starts before the
previous season.
Configure the seasons with increasing
start dates, see parameters
AF88
Season configuration
warning
You have configured a season
which starts before the
previous season.
Configure the seasons with increasing
start dates, see parameters
AF90
Speed controller
autotuning
The speed controller autotune
routine did not complete
successfully.
Check the auxiliary code (format XXXX
YYYY). “YYYY” indicates the problem
(see actions for each code below).
0000 The drive was stopped before
the autotune routine finished.
Repeat autotune until successful.
0001 The drive was started but was
not ready to follow the
autotune command.
Make sure the prerequisites of the
autotune run are fulfilled. See section
Before activating the autotune routine
(page
0002 Required torque reference
could not be reached before
the drive reached maximum
speed.
Decrease torque step (parameter
or increase speed step (
0003 Motor could not
accelerate/decelerate to
maximum/minimum speed.
Increase torque step (parameter
)
or decrease speed step (
).
0005 Motor could not decelerate
with full autotune torque.
Decrease torque step (parameter
or speed step (
).
AFAA
Autoreset
A fault is about to be autoreset. Informative warning. See the settings in
parameter group
.
AFE1
Emergency stop (off2) Drive has received an
emergency stop (mode
selection off2) command.
Check that it is safe to continue
operation. Then return emergency stop
push button to normal position. Restart
drive.
If the emergency stop was unintentional,
check the source selected by parameter
AFE2
Emergency stop (off1
or off3)
Drive has received an
emergency stop (mode
selection off1 or off3)
command.
AFE9
Start delay
The start delay is active and
the drive will start the motor
after a predefined delay.
Informative warning. See parameter
.
AFF5
Override new start
required
The Safe torque off function
was active and has been reset
while in Override.
A new start signal is required to start the
drive again.
Code
(hex)
Warning / Aux. code
(
aux code visible only
on assistant control
panel and drive
composer
)
Cause
What to do
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...