Parameters 233
Defines the derivation time for acceleration(/deceleration)
compensation. In order to compensate for a high inertia load
during acceleration, a derivative of the reference is added to
the output of the speed controller. The principle of a derivative
action is described under parameter
.
Note:
As a general rule, set this parameter to the value
between 50 and 100% of the sum of the mechanical time
constants of the motor and the driven machine.
The figure below shows the speed responses when a high
inertia load is accelerated along a ramp.
No acceleration compensation:
Acceleration compensation:
0.00
0.00…1000.00 s
Acceleration compensation derivation time.
10 = 1
Defines the acceleration (or deceleration) compensation filter
time constant. See parameters
8.0
0.0…1000.0 ms
Acceleration/deceleration compensation filter time.
1 = 1
Enables/disables the flux optimization function. Flux
Optimization reduces the total energy
consumption and noise when the drive operates below the
nominal load. This must be enabled for drives that usually
operate below nominal load.
Enable
Enables the flux optimization. Changes the magnitude of the
flux depending on the actual load.
1
Disable
Disables the flux optimization.
0
No.
Name/Value
Description
Def/FbEq16
Time
Speed reference
Actual speed
Time
Speed reference
Actual speed
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...