Parameters 365
Motor parameters
…
are used as the
motor model.
1
Defines the stator resistance
R
S
of the motor model.
With a star-connected motor,
R
S
is the resistance of one
winding. With a delta-connected motor,
R
S
is one-third of the
resistance of one winding.
0.00000 p.u.
0.00000…0.50000
p.u.
Stator resistance in per unit.
-
Defines the rotor resistance
R
R
of the motor model.
0.00000 p.u.
0.00000…0.50000
p.u.
Rotor resistance in per unit.
-
Defines the main inductance
L
M
of the motor model.
0.00000 p.u.
0.00000…10.00000
p.u.
Main inductance in per unit.
-
Defines the leakage inductance
L
S
.
0.00000 p.u.
0.00000…1.00000
p.u.
Leakage inductance in per unit.
-
Defines the stator resistance
R
S
of the motor model.
0.00000 ohm
0.00000…100.0000
0 ohm
Stator resistance.
-
Defines the rotor resistance
R
R
of the motor model.
0.00000 ohm
0.00000…100.0000
0 ohm
Rotor resistance.
-
Defines the main inductance
L
M
of the motor model.
0.00 mH
0.00…100000.00
mH
Main inductance.
1 = 10000
mH
Defines the leakage inductance
L
S
.
0.00 mH
0.00…100000.00
mH
Leakage inductance.
1 = 10000
mH
Motor configuration settings.
Selects the motor type.
Note:
This parameter cannot be changed while the drive is
running.
Asynchronous
motor
Standard squirrel cage AC induction motor (asynchronous
induction motor).
0
Selects the motor control mode.
Vector
Vector control. Vector control has better accuracy than scalar
control but cannot be used in all situations (see selection
below).
Requires motor identification run (ID run). See parameter
Note:
In vector control the drive performs a standstill ID run at
the first start if ID run has not been previously performed. A
new start command is required after standstill ID run.
Note:
To achieve a better motor control performance, you can
perform a normal ID run without load.
See also section
(page
0
No.
Name/Value
Description
Def/FbEq16
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...