282 Parameters
KTY83 analog I/O
KTY83 sensor connected to the analog input selected by
parameter
and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
12
1 × Pt1000 analog
I/O
Pt1000 sensor connected to a standard analog input selected
by parameter
and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
13
2 × Pt1000 analog
I/O
As selection
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
14
3 × Pt1000 analog
I/O
As selection
, but with three sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
15
Ni1000
Ni1000 sensor connected to the analog input selected by
parameter
and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
16
No.
Name/Value
Description
Def/FbEq16
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...