450 Fieldbus control through the embedded fieldbus interface (EFB)
14
REQ_LOCAL_LO
CK
1
Drive does not switch to local control mode (see
parameter
0
Drive can switch between local and remote control
modes.
15
Reserved
16
FB_LOCAL_CTL
1
Local mode for control from the fieldbus is requested.
Steal control from the active source.
0
(no op)
17
FB_LOCAL_REF
1
Local mode for reference from the fieldbus is requested.
Steal reference from the active source.
0
(no op)
18
Reserved for
RUN_DISABLE_1
Not yet implemented.
19
Reserved
20
Reserved
21
Reserved
22
USER_0
Writable control bits that can be combined with drive logic
for application-specific functionality.
23
USER_1
24
USER_2
25
USER_3
26…
31
Reserved
Bit
Name
Value
State/Description