Parameters 363
Defines the relative output voltage boost at zero speed (IR
compensation). The function is useful in applications with a
high break-away torque where vector control cannot be
applied.
See also section
IR compensation for scalar motor control
on
page
.
Typical IR compensation values are shown below.
WARNING!
Set IR compensation value as low as
possible. Large IR compensation value can lead to
overheating of the motor and damage to the drive, if
operated for longer periods at low speed.
3.50%
0.00…50.00%
Voltage boost at zero speed in percent of nominal motor
voltage.
1 = 1%
Selects the form for the
U
/
f
(voltage to frequency) ratio below
field weakening point. For scalar control only.
Linear
Linear ratio for constant torque applications.
0
Squared
Squared ratio for centrifugal pump and fan applications.
With squared U/f ratio the noise level is lower for most
operating frequencies.
1
No.
Name/Value
Description
Def/FbEq16
U
/
U
N
(%)
f
(Hz)
Field weakening point
Relative output voltage. No
IR compensation.
Relative output voltage. IR
compensation set to 15%.
15%
100%
50% of nominal
frequency
3-phase 380…415V drives
P
N
(kW) 0, 37 0, 75 1, 1 2, 2
4
7, 5
15
37 132
IR
compen
-sation
(%)
3, 5 3, 5 3, 2 2, 5
2
1, 5
1.3
1.1 0.6
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...