124 Control macros
T
erminal sizes
• (frames R0…R8): 0.14…1.5 mm
2
(all terminals)
• Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes
1)
Current [0(4)…20 mA,
R
in
< 500 ohm] or voltage [ 0(2)…10 V,
R
in
> 200 kohm]
input as selected with parameter
12.15 AI1 unit selection
.
2)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [ 0(2)…10 V,
R
in
> 200 kohm]
input as selected with parameter
12.25 AI2 unit selection
.
3)
Total load capacity of the auxiliary voltage 24V (X2:10) = 6.0 W (250 mA /
24 V). User can use this source for either of the I/O connections (DI1... DI2- RO1 or
DI3...DI6 - RO2~RO3).
4)
Connected with jumpers at the factory.
5)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
6)
Can be used to set up pressure alarm warning.
7)
Can be used for cold start prevention with connection to ‘temperature reached’
output of temperature controller or PLC
8)
Input signal
9)
Output signal
10)
For R0...R2 frames only
In addition, some inputs and settings are set automatically as follows:
For information on cable connection and drive operation, see
Control Connections
in
the
Hardware manual (3AXD50000044998)
No.
Name (Input/Setting)
Value
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...